Fire sprinkler

From Wikipedia, the free encyclopedia

Jump to: navigation, search

A fire sprinkler is the part of a fire sprinkler system that discharges water when the effects of a fire have been detected, such as when a predetermined temperature has been reached.

Contents

[edit] History

In the 1870s, the Parmelee sprinkler head was introduced in the United States.

[edit] US regulatory requirements

Fire sprinkler application and installation guidelines, and overall fire sprinkler system design guidelines, are provided by the National Fire Protection Association (NFPA) 13, (NFPA) 13D, and (NFPA) 13R.

Fire sprinklers can be automatic or open orifice. Automatic fire sprinklers operate at a predetermined temperature, utilizing a fusible link, a portion of which melts, or a frangible glass bulb containing liquid which breaks, allowing the plug in the orifice to be pushed out of the orifice by the water pressure in the fire sprinkler piping, resulting in water flow from the orifice. The water stream impacts a deflector, which produces a specific spray pattern designed in support of the goals of the sprinkler type (i.e., control or suppression). Modern sprinkler heads are designed to direct spray downwards. Spray nozzles are available to provide spray in various directions and patterns. The majority of automatic fire sprinklers operate individually in a fire. Contrary to motion picture representation, the entire sprinkler system does not activate, unless the system is a special deluge type.

Open orifice sprinklers are only used in water spray systems or deluge sprinklers systems. They are identical to the automatic sprinkler on which they are based, with the heat sensitive operating element removed.

Automatic fire sprinklers utilizing frangible bulbs follow a standardized color coding convention indicating their operating temperature. Activation temperatures correspond to the type of hazard against which the sprinkler system protects. Residential occupancies are provided with a special type of fast response sprinkler with the unique goal of life safety.

Maximum Ceiling Temperature Temperature Rating Temperature Classification Color Code (with Fusible Link) Glass Bulb Color
100°F / 38°C 135-170°F / 57-77°C Ordinary Uncolored or Black Orange (135°) or Red (155°)
150°F / 66°C 175-225°F / 79-107°C Intermediate White Yellow (175°) or Green (200°)
225°F / 107°C 250-300°F / 121-149°C High Blue Blue
300°F / 149°C 325-375°F / 163-191°C Extra High Red Purple
375°F / 191°C 400-475°F / 204-246°C Very Extra High Green Black
475°F / 246°C 500-575°F / 260-302°C Ultra High Orange Black
625°F / 329°C 650°F / 343°C Ultra High Orange Black

From Table 6.2.5.1 NFPA13 2007 Edition indicates the maximum ceiling temperature, nominal operating temperature of the sprinkler, color of the bulb or link and the temperature classification.

[edit] References

[edit] Other links


 v  d  e 
Fire protection
General: Active fire protectionFire alarm system

Fire suppression: Fire extinguisherFire sand bucketFire sprinklerGaseous fire suppression
Detection/alarm: Control panelHeat detectorPull stationNotification applianceSmoke detector
Practices: Fire drillFire drill regulations

Image:Pixel.gif
Views
Personal tools

Toolbox